
Written and maintained by the PhDino author · Last reviewed 21 September 2026 · Checked against 1 independent reference calculation · how PhDino checks its numbers
How much battery capacity an off-grid or backup solar system needs to ride out days without sun.
A battery bank's job is to store energy produced during sunny hours for use when the sun isn't producing — overnight at minimum, and through cloudy stretches for a system meant to run fully off-grid. Sizing it starts from the same daily energy need used to size the array, multiplied by how many days of backup ("autonomy") the system needs to survive with no solar input at all.
Batteries can't be run all the way to empty without damaging them or drastically shortening their lifespan — depth of discharge (DoD) is the fraction of a battery's total capacity that's actually safe to use. A battery with a 50% DoD limit needs twice its usable capacity in total rated capacity, since half of it is reserved as a buffer never meant to be drawn down.
Energy needed = daily energy need × autonomy days Usable capacity (Ah) = energy needed (Wh) ÷ system voltage Required rated capacity = usable capacity ÷ depth of discharge
Use this to find how much battery capacity, in amp-hours at your system voltage, it takes to carry a daily energy need through a chosen number of days with no sun or no grid. It is the second step after the array in an off-grid or backup design, and the one that most controls the cost.
The key idea is that you cannot use all of a battery: discharging deeply shortens its life, so the calculator divides by the usable fraction, the depth of discharge. That is why the chemistry you choose changes the bank size so much.
The same cabin uses 6 kWh per day and should ride through 2 days without charging. Lithium iron phosphate batteries will be used down to 80% depth of discharge on a 24 V bank. How much capacity?
| You enter | Value |
|---|---|
| Daily Energy Need | 6 kWh |
| Days of Autonomy | 2 days |
| Max Depth of Discharge | 80 % |
| System Voltage | 24 V |
| The calculator returns | Value |
|---|---|
| Required Battery Capacity | 625 Ah |
Worked by hand:
The cabin needs a 625 Ah, 24 V lithium bank, which is 15 kWh nominal. Built from 12 V, 100 Ah batteries, that is two in series for the voltage in each of 7 parallel strings, 14 batteries in all. With lead-acid limited to 50 percent depth of discharge the same duty would need 1,000 Ah, and the same energy on a 48 V bank would need only 312.5 Ah.
The result is the capacity that must be installed to deliver the energy at the stated depth of discharge. Real banks lose a little on top of that, and treating the figure as a floor rather than a target is wise. Adding about ten percent, 688 Ah here, covers inverter losses, the round-trip efficiency of charging and an ageing battery.
It depends on how long a gap without charging you must survive. One to two days is common with a generator or reliable sun to recover, and three to five for critical loads. Each extra day adds a full day's energy to the bank.
About 50 percent for lead-acid batteries if you want them to last, and 80 percent or more for lithium iron phosphate. Follow the manufacturer's recommendation for cycle life.
Amp-hours times volts is the energy. The same energy at four times the voltage takes a quarter of the amp-hours, and the current the wiring must carry falls in the same proportion.
Yes: series adds voltage and parallel adds capacity. Keep the number of parallel strings within the manufacturer's limit, and use identical batteries throughout.
A critical review of using the Peukert equation for determining the remaining capacity of lead-acid and lithium-ion batteries Doerffel, D. & Sharkh, S. A. (2006), Journal of Power Sources. A critical look at the Peukert equation, the rule behind “a battery gives less capacity at high discharge rates”, and where it stops being reliable.
PhDino earns a commission on qualifying purchases made through this link, at no extra cost to you.
Renewable Energy: A Very Short Introduction by Nick Jelley — A concise, physics-grounded look at solar, wind, and the numbers behind sizing a system. (Bookshop.org UK, UK delivery only)
→ The full PhDino bookshelf on Bookshop.org (UK delivery only)
